What Is Thermal Bridging? Where Buildings Leak Heat and How to Reduce It

Writer: Sara
Sara
7 hours ago
11 min read
Hand-drawn sketchbook section of a concrete balcony slab passing through an insulated exterior wall, with arrows showing heat escaping along the slab, illustrating thermal bridging

In one widely cited study of high-rise residential towers in British Columbia, cantilevered concrete balconies made up about 2.7% of the opaque wall area, yet they accounted for roughly 15% to 30% of the heat flowing through those walls. That gap between how small something looks on a drawing and how much heat it actually moves is the whole story of thermal bridging.


Thermal bridging is one of the least visible and most underestimated problems in building design. It explains why R-19 batts in a steel stud wall deliver something closer to R-7, why mould appears in a neat line along a ceiling edge, and why North American energy codes have recently added detailed rules for slab edges, parapets and window frames. This guide covers what a thermal bridge is, how it is measured, where it usually occurs, and the design strategies that reduce it.



What Is a Thermal Bridge?

A thermal bridge is a part of the building envelope that conducts heat much more readily than the materials around it. Heat follows the path of least resistance, so it crowds into these elements and bypasses the insulation. ASHRAE Standard 90.1-2022 uses a similar definition: an element with higher thermal conductivity than its surroundings that creates a path of least resistance for heat transfer.


The standard, like most current guidance, groups thermal bridges into three types:


  • Clear-field thermal bridges: elements repeated across the whole area of an assembly, such as studs, masonry ties, girts and fasteners. They are usually built into the published U-factor of the assembly.

  • Linear thermal bridges: elements that run along a length of the envelope, such as floor slab edges, balconies, parapets, shelf angles and window perimeters. Their extra heat loss is expressed per metre or per foot of length.

  • Point thermal bridges: single penetrations, such as a steel beam passing through a wall, a column through a roof, or an anchor for a canopy or rooftop equipment.


A related idea is the geometric thermal bridge. At an outside corner, the exterior surface is larger than the interior one, so more heat escapes even when the insulation is perfectly continuous. These effects are usually modest and unavoidable, but they help explain why corners are often the coldest spots in a room.


Why a Thin Piece of Steel Matters So Much

The severity of a thermal bridge depends on how conductive the bridging material is compared with the insulation it interrupts. Typical design values for thermal conductivity (λ, in W/m·K) show how wide that range is:


  • Aluminium: about 220

  • Steel: about 50

  • Reinforced concrete: about 2.3 to 2.5

  • Softwood timber: about 0.13

  • Mineral wool or expanded polystyrene insulation: about 0.035 to 0.04


Steel conducts heat more than a thousand times faster than mineral wool. Softwood performs far better, but it still conducts roughly three to four times more than the insulation beside it, which is why even timber studs lower the real performance of a wood-frame wall.


This is also why cross-sectional area is a poor guide. The Building Envelope Thermal Bridging Guide, prepared by Morrison Hershfield for BC Hydro, notes that steel studs occupy only a small part of a wall's area, yet they reduce the effectiveness of the cavity insulation by 40% to 60%, depending on stud spacing and whether the wall also has exterior insulation.


Steel is chosen for strength and speed of construction, not thermal performance. For the structural side of the story, read our overview of steel structure in architecture and construction.



How Thermal Bridging Is Measured

Three values appear again and again in envelope calculations, energy models and product data sheets:


  • Effective R-value (or overall U-factor): the performance of the whole assembly, including framing and other repeated bridges, rather than the nominal R-value printed on the insulation.

  • Psi-value (Ψ): the extra heat flow along a linear thermal bridge, in W/(m·K) or Btu/(h·ft·°F). A slab edge or a window perimeter has a psi-value.

  • Chi-value (χ): the extra heat flow through a single point thermal bridge, in W/K or Btu/(h·°F).


In practice, the designer calculates the heat loss of the clear wall, then adds each linear bridge multiplied by its length and each point bridge multiplied by its count. The total can be converted back into an effective U-factor for the whole elevation. Psi and chi values come from two- and three-dimensional heat-flow modelling, from manufacturer testing, or from published catalogues such as the BC Hydro guide and Table A10.1 of ASHRAE 90.1-2022.


The Passive House Institute uses psi-values to set one of the strictest benchmarks in the industry. A linear detail with an external psi-value of 0.01 W/(m·K) or less is treated as 'thermal bridge free' and can be left out of the energy balance. Anything above that has to be calculated.


Framing: The Thermal Bridge in Every Wall

Studs are the most common thermal bridges of all, simply because there are so many of them. Building science research cited by the U.S. Department of Housing and Urban Development puts the framing factor of a typical wood-framed house as high as 25%, meaning up to a quarter of the wall area is solid wood rather than insulation once studs, plates, headers and extra corner framing are counted. With advanced framing, that figure can fall to around 15%.


Steel framing is a much bigger problem. Energy code tables based on ASHRAE data give these effective values for the stud-and-cavity layer alone:


  • 3½-inch steel studs at 16 inches on center with R-13 batts: about R-6.0

  • The same studs at 24 inches on center: about R-7.2

  • 6-inch steel studs at 16 inches on center with R-19 batts: about R-7.1


More than half of the insulation value disappears through the steel. This is the main reason energy codes push steel-framed walls toward continuous exterior insulation.


Practical ways to reduce framing losses:


  • In wood frame, use 2x6 studs at 24 inches on center where the structure allows, single top plates, insulated headers, and corner and wall-intersection details that leave room for insulation.

  • Add continuous insulation outside the sheathing so the studs no longer connect the inside and outside surfaces.

  • In steel frame, treat cavity insulation as a secondary layer and rely on exterior insulation for most of the thermal performance.


The Department of Energy's Building America program reported energy savings of 13% from advanced framing in one study, coming partly from fewer studs and partly from deeper, better-insulated cavities.



Floor Slab Edges and Balconies

Concrete floors that extend to the outer face of a building are among the most damaging linear thermal bridges. In walls insulated on the inside, which is common in cast-in-place concrete towers, every floor slab runs straight past the insulation to the outside air. The insulation is interrupted at every storey, no matter how thick it is.


Balconies make this worse because the slab does not just touch the outside; it projects into it and behaves like a cooling fin. The British Columbia analysis mentioned at the start of this article found that, in one high-rise residential case with exterior insulation finish system (EIFS) cladding on concrete, balconies and exposed slab edges carried about 40% of the opaque wall heat flow. With thermally broken balconies and improved details, that share dropped to about 20%.


Designers have three main ways to deal with projecting slabs:


  1. Structural thermal breaks: manufactured connectors that carry balcony loads through a block of insulation using stainless steel bars and compression modules. They do not eliminate the bridge, but they reduce it substantially.

  2. Separately supported balconies: balconies that stand on their own posts or hang from their own frame, tied back to the building with a limited number of point connections.

  3. Exterior insulation over slab edges: where nothing projects, continuous exterior insulation can cover the slab edge completely, one of the main thermal advantages of exterior-insulated walls.


Passive House research adds an important point: thermal bridges become relatively more significant as walls improve. In one example published by the International Passive House Association, the same projecting balcony slab had a psi-value of 0.24 W/(m·K) in an uninsulated wall and 0.69 W/(m·K) in a well-insulated Passive House wall, nearly three times higher. Once the rest of the wall stops leaking, the slab becomes the easiest way out.


Windows and Door Perimeters

Every window opening creates a linear thermal bridge around its frame. Its size depends heavily on where the window sits relative to the insulation layer and how the gap between frame and wall is detailed. A window set in line with the insulation performs much better than one pushed to the outer face of the wall while the insulation sits further in, because the heat path around the frame becomes short and direct.


Modelling in the BC Hydro guide for the sill of an aluminum window in an exterior-insulated steel stud wall shows how much ordinary detailing can change:


  • Base case: a psi-value of about 0.41 W/(m·K)

  • With a plywood liner in the rough opening: about 0.24

  • With a plywood liner and the window moved toward the exterior: about 0.21

  • With R-4 insulation wrapped into the opening: about 0.21


Roughly halving the heat loss at the sill came from liners, positioning and a little insulation, not from a more expensive window. For low-rise wood-frame buildings with 30% glazing, the same guide found that the junction between aluminum windows and the wall could account for 30% to 40% of the heat flow through the opaque envelope. Vinyl windows in a similar position cut that contribution roughly in half.



Roof Edges and Parapets

Parapets are difficult to insulate because they are exposed to the outside on three sides. In concrete and masonry buildings the parapet is usually a continuation of the exterior wall, so it draws heat up and out from the roof edge and the top floor.


Wrapping insulation over and around a parapet helps, but the BC Hydro guide found it reduced parapet heat loss by only about 60%. A thermally broken parapet, where a structural thermal break lets the roof insulation line up with the wall insulation, reduced heat loss by more than 85% compared with common practice. The wrapped version still leaves the parapet's extra surface area exposed and connected to the warm structure below.


ASHRAE 90.1-2022 now addresses roof and wall intersections directly for roofs with insulation entirely above the deck, covering roof edges, perimeter parapets, and parapets within the field of a roof, such as fire walls.


Cladding Attachments and Shelf Angles

Exterior insulation only works as well as the way the cladding is fixed through it. Steel clips, girts, brackets and the shelf angles that carry brick veneer all pass through the insulation layer.


The BC Hydro guide compared attachment systems for a steel stud wall with R-16.8 of exterior insulation and attachments at 24 inches vertically and 16 inches horizontally. With no penetrations at all, the assembly would reach about R-19.6. Real systems ranged from about R-19.2 for fibre-reinforced plastic clips with steel girts down to about R-14.7 for generic vertical steel clips and sub-girts. The insulation thickness was identical in every case; only the attachment changed.


Two cautions apply when comparing products:


  • Compare systems at the spacing the project's wind load actually requires, not at a convenient standard spacing. The same guide showed that some systems look better at 24-inch spacing than they do once their real structural spacing is used.

  • Continuous steel shelf angles supporting masonry act as long linear bridges at every floor. Standing the angle off the slab on intermittent brackets lets insulation run behind it, and ASHRAE 90.1-2022 now sets requirements for this condition.



Thermal Bridges, Condensation and Mould

Energy is only half of the problem. A thermal bridge also creates a cold patch on the interior surface. Air next to a cold surface has a higher relative humidity, and if the surface stays humid for long enough, mould can grow without any visible condensation. Guidance from thermal break manufacturers and UK research on dwellings commonly treats a sustained surface relative humidity of around 80% as the level of concern.


To judge this risk independently of the weather on a particular day, building scientists use the temperature factor, written fRsi:


fRsi = (interior surface temperature - outdoor air temperature) ÷ (indoor air temperature - outdoor air temperature)


A value near 1.0 means the surface stays close to room temperature, while severe thermal bridges fall below 0.5. UK guidance in BRE Information Paper IP 1/06 calls for at least 0.75 in dwellings and at least 0.5 in offices and retail spaces, with higher values, around 0.9, recommended for very humid spaces such as swimming pools.


A worked example makes the factor easier to read. With 20°C inside and -5°C outside, a steel I-beam passing straight through the insulation in one published analysis had a minimum interior surface temperature of about 7.5°C, which gives an fRsi of 0.50. Replacing the continuous beam with a structural thermal break raised that surface to about 15.2°C and the factor to 0.81, comfortably above the residential threshold.


Surface condensation at a cold spot is a different issue from water vapor moving through a wall. This guide to vapor barriers and vapor retarders explains where vapor control layers belong in walls, crawl spaces and slabs.


What the Energy Codes Now Require

For years, North American energy codes mostly regulated how much insulation each assembly contained and assumed perfect connections between assemblies. That has changed.


ASHRAE 90.1-2022 introduced Section 5.5.5, which requires mitigation of linear and point thermal bridges in five categories:


  1. Roof and wall intersections (5.5.5.1)

  2. Intermediate floor intersections, including balconies and other projections (5.5.5.2)

  3. Exterior cladding support, such as shelf angles (5.5.5.3)

  4. Opaque wall and vertical fenestration intersections (5.5.5.4), with compliance options based on the window's position relative to the insulation

  5. Other elements and assembly intersections (5.5.5.5), such as cantilevered entrance canopies and supports for rooftop equipment


These requirements are prescriptive, but projects that cannot meet them can use the envelope trade-off path or whole-building energy modelling, entering psi and chi values for the unmitigated bridges. There are exceptions for warmer climate zones and semiheated spaces, and for materials with a thermal conductivity below 3.0 Btu·in/(h·ft²·°F), or 0.433 W/(m·K), which covers wood. The 2024 International Energy Conservation Code also added thermal bridging provisions for commercial buildings, including rules for balconies and floor decks that penetrate the thermal envelope. Adoption varies by state and city, so the edition in force locally is what applies to a given project.



Seven Common Thermal Bridging Mistakes

  1. Trusting the nominal R-value. The number on the insulation package is not the performance of the wall. Use effective values that include framing and attachments.

  2. Ignoring elements because they look small on plan. Balconies, shelf angles and slab edges are a small share of the wall area but can carry a large share of the heat.

  3. Adding insulation instead of fixing details. The BC Hydro analysis found that improving interface details is generally more cost effective than adding insulation to walls that are already well insulated.

  4. Letting insulation layers miss each other. Wall insulation that does not meet the roof, window or foundation insulation leaves a gap, even when each assembly is good on its own.

  5. Bringing interior shear walls or columns out to the façade. In the BC analysis, simply stopping concrete shear walls short of the exterior wall saved energy at almost no extra cost.

  6. Choosing cladding clips by catalogue spacing. Real thermal performance depends on the spacing the structural design actually needs.

  7. Leaving thermal bridges to the energy modeller. By the time the model is built, structure and façade are fixed. Slab edges, balconies and window positions are cheapest to improve in schematic design.


How to Find Thermal Bridges in an Existing Building

In an existing building, the quickest diagnostic tool is an infrared camera. The U.S. Department of Energy notes that thermographic images are usually most accurate when indoor and outdoor air temperatures differ by at least 20°F (about 14°C), which is why scans in colder regions are generally done in winter. On an interior scan, studs show up as a regular pattern of cooler lines, while slab edges and lintels appear as continuous cold bands.


Other signs worth checking:


  • Mould or damp patches where exterior walls meet ceilings or floors, especially in corners

  • Condensation on window frames and sills during cold weather

  • Faint dark lines on ceilings or walls that follow the framing, which can form where colder strips attract dust and moisture

  • Cold floors above unheated garages or along the edge of a slab


Retrofitting is harder than getting the details right at the start, but several moves are proven: adding continuous exterior insulation during a recladding project, insulating window returns when windows are replaced, and wrapping exposed slab edges or beams where access allows.


Thermal fixes work best alongside basic air sealing and insulation upkeep, which our practical winter home checklist walks through step by step.


Designing With Thermal Bridges in Mind

Thermal bridging rewards attention early. The most effective decisions come before any detail is drawn: keeping the structure inside the insulation where possible, choosing exterior-insulated assemblies, limiting projecting slabs, and placing windows in line with the insulation layer. Structural thermal breaks, low-conductivity clips and careful window details then deal with what cannot be avoided.


A simple check works well in design reviews. Take a building section and trace the insulation layer with a pen without lifting it. Every place where the pen has to jump across concrete, steel or a window frame is a thermal bridge that needs a psi-value, a better detail, or both.